Permit Number: T11CM01588
Parcel: 13104399H

Address:
4777 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM01588
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2011 RONALD BROWN ADA REVIEW Passed
08/11/2011 MARTIN BROWN FIRE REVIEW Approved
08/15/2011 GERRY KOZIOL WWM REVIEW Denied NEED CIVAL DRAWINGS/SITE PLAN SHOWING LOCATION/METHOD OF CONNECTIONS TO EXSISTING BUILDINGS/MODULARS TO PUBLIC SEWER
08/16/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide special inspector certifications as per sheet S1.1.
prior to permit issuance.
2. Overflow roof drain detail does not work. Reference Mechanical plumbing comments for code compliance directions.
END OF REVIEW
08/16/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cox Communications - 4777 E. 29th
T11CM01588
Building Plan (1st Review)

TRANSMITTAL DATE: August 16, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the Site plan has been approved. Plumbing Review section still has site comments to comply with.

3. As the site, landscape & building plans have been submitted together combine the plans together and revise the drawing index to reflect all sheets as one set prior to the next submittal.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved Site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\bldg\t11cm01588.doc
08/16/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/17/2011 ROBERT SHERRY WATER REVIEW Approved
08/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations for the building envelope (use the climate zone for Pima County < 4,000 feet). Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
08/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the new 3" building sewer shown on the north side of the building addition. The site plan for the building does not show any new building sewer for this building. Reference: section 106.3.1, IPC 2006.
2. Provide calculations to show that the size of the two overflow openings in the roof drain collector boxes have a drainage capacity equal to the minimum required scupper size. Reference: Section 1107.1, IPC 2006.
08/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01588
4777 E 29th ST

1. Please provide information concerning the operation consisting of Panel I1 having two feeders going to Panel I2 and the Kirt Key interlocks.
2. Provide information regarding the New Inverter, having a 300 amp input and a 250 amp output and how it affects Panel I2.
3. Provide Panel Schedules including loads for Panels I1 and I2.

Ray Majuta,
PDSD,C of T,
Elect Pln CK,
8/25/11,
520/837/4988
08/24/2011 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
08/29/2011 SUE REEVES REJECT SHELF Completed