Permit Number: T11CM01580
Parcel: 117200250

Address:
270 S STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01580
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2; SHEET A2.2.3 (FLOOR PLAN LEGEND); SHEET A4.0.3 (SECTION 2): THE SECTION INDICATES THE NEW WALL STUDS TO BE 20 GAUGE, 6" METAL STUDS AT 24" O.C., WHILE THE FLOOR PLAN LEGEND INDICATES 3 5/8", 20 GAUGE METAL STUDS AT 16" O.C. CLARIFY AND COORDINATE THE METAL STUD SIZES.
2. GENERAL: PROVIDE WRITTEN RESPONSE TO THE REVIEW COMMENT

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2011 DELMA ROBEY OUT TO CUSTOMER Completed