Permit Number: T11CM01485
Parcel: 12902045B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01485
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
05/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/17/2011 ROBERT SHERRY WATER REVIEW Approved
05/17/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide for an accessibile front reception counter as required by ICC (ANSI 117.1), Section 904
2. Please coordinate the architectural drawing work to the plumbing drawing work as to removing plumbing fixtures or not.
3. Toilets do not meet ANSI 117.1 clearances for accessibility. Please do not provide accessibility signage identifying them as accessible.
END OF REVIEW.
05/17/2011 JASON GREEN ENGINEERING REVIEW Approved
05/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/17/2011 MARTIN BROWN FIRE REVIEW Approved
05/17/2011 RONALD BROWN ADA REVIEW Completed
05/17/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/23/2011 CAGUILA1 WWM REVIEW Needs Review