Permit Number: T11CM01097
Parcel: 117031120

Address:
847 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM01097
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2011 DAVE MANN FIRE REVIEW Approved
05/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01097
847 N Stone Av
34KW DC PV System



Electrical Pland denied for the following:
1. Per Commercial Submittal Requirements,plans must be legible,with a minimun text size of 1/8''.
2. Commercial PV Plans to be sealed by EE.
3. Provide specification sheet on Combiner,and show location on plan that it is to be installed.
4. Sheet 4 of 5, the fused disconnect providing the #4's going into the 200 amp MB Panel at line terminals, provide information on how this will be installed . Unless the termination is listed for this application having it's own terminals a splice will not be allowed in the enclosure.
5. Does Sheet 4 of 5 describe a somewhat correct elevation diagram of how equipment will be installed, show where wall of building seperates equipment.
6. Show where the 200 amp disconnect will be located.

Ray Majuta,
Elect Pln Ck,
PDSD,City of Tuc,
5/3/11