| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/03/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM01097 847 N Stone Av 34KW DC PV System Electrical Pland denied for the following: 1. Per Commercial Submittal Requirements,plans must be legible,with a minimun text size of 1/8''. 2. Commercial PV Plans to be sealed by EE. 3. Provide specification sheet on Combiner,and show location on plan that it is to be installed. 4. Sheet 4 of 5, the fused disconnect providing the #4's going into the 200 amp MB Panel at line terminals, provide information on how this will be installed . Unless the termination is listed for this application having it's own terminals a splice will not be allowed in the enclosure. 5. Does Sheet 4 of 5 describe a somewhat correct elevation diagram of how equipment will be installed, show where wall of building seperates equipment. 6. Show where the 200 amp disconnect will be located. Ray Majuta, Elect Pln Ck, PDSD,City of Tuc, 5/3/11 Ray.majuta@tucsonaz.gov |
| 05/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |