Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/12/2011 GERRY KOZIOL WWM REVIEW Approved
05/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00766
4370 N Oracle Rd
Nordstrams Rack


The Electrical Plans have been denied for the following:

1. The AIC at the 800 amp service is shown @ 23,798 amps,
the GE Spec Sheet for the MDP Section is listed for 14 KAIC?
2. Panel A on the GE Spec Sheet is listed for 14 KAIC, and the plan shows AFC 17,879 A, with a requirement of 25 KAIC.
3. Panel M on the GE Spec Sheet is listed for 14 KAIC, and
the plan shows AFC 18,531 A, with a requirement of 18 KAIC.
All other items have been verified.

Ray T Majuta,
Elect Pln CK,PDSD_City of Tucson,
5/20/11
Ray.Majuta@tucsonaz.gov
05/31/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/31/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved