Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00766
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/12/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00766 4370 N Oracle Rd Nordstrams Rack The Electrical Plans have been denied for the following: 1. The AIC at the 800 amp service is shown @ 23,798 amps, the GE Spec Sheet for the MDP Section is listed for 14 KAIC? 2. Panel A on the GE Spec Sheet is listed for 14 KAIC, and the plan shows AFC 17,879 A, with a requirement of 25 KAIC. 3. Panel M on the GE Spec Sheet is listed for 14 KAIC, and the plan shows AFC 18,531 A, with a requirement of 18 KAIC. All other items have been verified. Ray T Majuta, Elect Pln CK,PDSD_City of Tucson, 5/20/11 Ray.Majuta@tucsonaz.gov |
| 05/31/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 06/06/2011 | SUE REEVES | REJECT SHELF | Completed |