Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00766
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-001; CODE SUMMARY: UNDER 'BUILDING CODE', THE EXISTING FLOOR AREA IS NOTED AS 33,200 SF, WHILE UNDER 'MEANS OF EGRESS', IT IS LISTED AS 33,577 SF (DEVELOPMENT PLAN INDICATES 33,496 SF). CLARIFY. 2. SHEET A-001; CODE SUMMARY: THE CITY OF TUCSON REQUIRES ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT (UPPER AND LOWER CASE). REVISE. 3. SHEET A-001; DRAWING INDEX: A STRUCTURAL SHEET S-002 IS LISTED IN THE INDEX, BUT NOT INCLUDED IN THE REVIEW SET. CLARIFY. 4. SHEET M-122; DRAWING NOTE 1: DID NOT LOCATE ANY DETAILS ON THE STRUCTURAL SHEET FOR THE SUPPORT SYSTEMS OF THE NEW ROOFTOP EQUIPMENT OR OPENINGS IN THE ROOF. VERIFY AND PROVIDE AS REQUIRED. 5. SHEET M-122; STRUCTURAL CALCULATIONS: DID NOT LOCATE ANY CALCULATIONS FOR THE NEW ROOFTOP EQUIPMENT LOADS ON THE EXISTING ROOF. VERIFY AND PROVIDE CALCULATIONS AND DETAILS AS REQUIRED. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/11/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED ADRESSING REVIEW: SEE DP 33/49 S/B 4320 N ORACLE RD |
| 04/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the pipe sizes for the condensate drain system per Section 307.2.2, IMC 2006, as amended by the City of Tucson. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
| 04/14/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the note on the fixture connection schedule (P-001) which calls for the water closet drains to drop individually through the floor as compared to the waste and vent riser diagram on sheet P-002. 2. The branch piping sizes called out for the flush valves (1" for P-1 and ¾" for P-2) will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 3. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. |
| 04/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00766 4370 N Oracle RD TI Nordstrams Rack The Electrical Plans have been denied for the following: 1. Provide a fault current calculation showing fault current beginning at service and on through to individual panels, and show how the electrical equipment will be protected as per NEC 2005-110.9,110.10, and 110.22. 2. Provide information in the form of specification sheets concerning the Pre-manufactured Panel Group. 3.Provide Outdoor Lighting caculations as per The City of Tucson/Pima County Ordinance-Ord # 10135, which can be found on the City of Tucson web site.Call for info if need. 4.Sheet E-305 on the EAS Pedistal Elevation, a receptacle is shown above the accessible ceiling, is there intention to plug in equipment? 2005 NEC 400.8 restricts the use of cable in the form of a plug and cap to be above a suspended or dropped ceiling.? 5.Sheet E-401, fully describe the grounding system required by NEC for the 800 amp service including water, any-other metalic pipe, rebar ect. 6. Sheet E-401 notes on plan that the 800 amp main disconnect is existing, does this mean it's been previously permitted ? If so provide a loaction, and that it has been permitted befor, I cannot find it. Please provide a copy of the service plan if previously installed. Ray T Majuta, Elect Pln Ck,PDSD, City of Tucson, 4/25/11, Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/27/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/27/2011 | SUE REEVES | REJECT SHELF | Completed |