Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11BU01447
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | APPROVED FOR WILLIAM BALAK |
| 03/26/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. DRAWING WERE NOT PROVIDED FOR THE 30' X 48' METAL BUILDING |
| 03/27/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/01/2012 | CARL SCHULTZ | FIRE | REVIEW | Approv-Cond | Fire Comments: Provide a fire hydrant or fire sprinklers per IFC 508.5.1 as amended. |
| 05/01/2012 | CARL SCHULTZ | FIRE | REVIEW | Approv-Cond | Fire Flow requirements were determined using NFPA 1142 as referenced in the 2006 IFC. The required 3,175 gallons of storage can be met utilizing the existing water tanks onsite. The owner will provide a proper fire hose connection for firefighter use and sign the area to prevention the connection from being obstructed by the parking of vehicles. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/02/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 04/02/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |