Permit Number: T11BU01447
Parcel: 13631002P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11BU01447
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2012 STEVE SHIELDS ZONING REVIEW Approved APPROVED FOR WILLIAM BALAK
03/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. DRAWING WERE NOT PROVIDED FOR THE 30' X 48' METAL BUILDING
03/27/2012 PAUL MACHADO ENGINEERING REVIEW Approved
05/01/2012 CARL SCHULTZ FIRE REVIEW Approv-Cond Fire Comments:

Provide a fire hydrant or fire sprinklers per IFC 508.5.1 as amended.
05/01/2012 CARL SCHULTZ FIRE REVIEW Approv-Cond Fire Flow requirements were determined using NFPA 1142 as referenced in the 2006 IFC. The required 3,175 gallons of storage can be met utilizing the existing water tanks onsite. The owner will provide a proper fire hose connection for firefighter use and sign the area to prevention the connection from being obstructed by the parking of vehicles.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/02/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
04/02/2012 FERNE RODRIGUEZ REJECT SHELF Completed