Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2011 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: February 4, 2011
TO: Peter Abraham, P.E., Tucson Water, 310 West Alameda, Tucson Arizona 85747
SUBJECT: Tucson Water Southern Avra Valley Storage And Recovery Project (SAVSARP) Phase 1 Well SA-014A Engineering Review
ADDRESS: 3330 S Sandario Rd
LOCATION: T14S, R11E, Section 28
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN INFO: FIRM Panel: 040192200K (effective date 2/8/99), SFHA zone: A01
ACTIVITY NUMBERS: T11BU00020 / T11OT00035

SUMMARY: PDSD Engineering Division has reviewed the plan set and recommends approval of floodplain use permit and grading permit. Drainage report was reviewed for Tucson Water SAVSARP Well SA-014A only.

GRADING PERMIT CONDITIONS:
1) The following conditions apply to grading permit T11BU00020:
a) This permit is for the initial phase of the Tucson Water SAVSARP well improvements SA-014A phase 1 only.
b) The Southern Avra Valley Storage And Recovery Project (SAVSARP) Well SA-014A Phase 1 plans - Tucson Water Plan No.1-032-2010 (SA-014A) and specifications are a part of the grading permit. See also Floodplain Analysis Summary Report for Southern Avra Valley Storage and Recovery Project (SAVSARP) Planned Recovery-Well Pad Sites by TetraTech dated December 9, 2009, sealed 12/09/09 Michael Zeller, P.E.
c) Minimum pad elevation and well structure shall be set above the jurisdictional water surface to the elevation, as shown on the approved plans and drainage report, and shall be certified by an RLS.
d) Submit completed elevation certificates to City of Tucson Planning & Development Services Department Engineering Division for acceptance. For SAVSARP Well SA-014A, submit first elevation certificate after compaction and completion of the fill pad, and final elevation certificate indicating minimum elevation of base flange of well casing. The Floodplain Analysis Summary Report states that the upstream WSEL is 2305.81 and interpolated depth of flood at the well cover of 0.00, and that the well casing shall be 2-ft above any flood level. Elevation certificates may be submitted to show minimum pad grade of 2314.14, and well casing base flange at minimum 2316.14 (using existing grade at well casing 2313.14).
e) Submit a copy of the as-builts, with copies of compaction testing reports, to City of Tucson Planning & Development Services Department upon completion.
2) All conditions of Pima County Regional Flood Control District Floodplain Use Permit No.10-010 approved 2/16/10 shall apply.
3) Additional grading and floodplain review by the City of Tucson Planning & Development Services Department will be required for permits for the future structures or other future phase improvements on the constructed pad. At the time when permits are required for the future control building, submit copy of final elevation certificate with plans and drainage statement.

If you have any questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department