Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11BU00018
Parcel: 211350170

Review Status: Completed

Review Details: GRADING

Permit Number - T11BU00018
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2011 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: January 25, 2011
TO: Peter Abraham, P.E., Tucson Water, 310 West Alameda, Tucson Arizona 85747
SUBJECT: Tucson Water Southern Avra Valley Storage And Recovery Project (SAVSARP) Phase 1 Well SA-001A Engineering Review
ADDRESS: 2680 S Sandario Rd
LOCATION: T14S, R11E, Section 28
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN INFO: FIRM Panel: 040192200K (effective date 2/8/99), SFHA zone: A01
ACTIVITY NUMBERS: T11BU00018 / T11OT00036

SUMMARY: PDSD Engineering Division has reviewed the plan set submittal for Floodplain Use Permit and Grading Plan review, and does not recommend approval of the floodplain use permit and grading permit until the following comments are addressed. The drainage report was reviewed for Tucson Water SAVSARP Well SA-001A only.

GRADING PLAN COMMENTS:
1) DS Sec.11-01.4.1.C, Admin.Dir.1.07-6.III.A: The Floodplain Analysis Summary Report states that the upstream WSEL is 2296.52 and that the well cover shall be 2-ft above this flood level. Clarify / correct existing grade elevation at well casing, WSEL at well casing, and top of structure (to indicate at minimum 2-ft above WSEL) on the following details/sheets:
a) On sheet 2/5, planview detail Site, Grading & Enclosure Plan.
b) On sheet 2/5, Section A.
c) On sheet 4/5, detail 1 Turbine Pump Installation.

Resubmit the package including 2 copies of the revised plans. If you have any questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
01/26/2011 MICHAEL ST. PAUL ZONING REVIEW Passed
01/26/2011 MICHAEL ST. PAUL NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2011 SUE REEVES OUT TO CUSTOMER Completed