Permit Number: T10OT02668
Parcel: 13801004D

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T10OT02668
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2011 ELIZABETH EBERBACH ENGINEERING REVIEW Approved The following 14 conditions apply to permit T10OT02668:
1) Call for Pre-construction meeting and final inspections. For a PDSD Engineering Inspection, call IVR (740-6970), or contact PDSD Engineering at 837-4991, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html
2) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times. Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T10OT02668. FOR INFORMATION PLEASE CALL 791-5550."
3) All work shall conform to the approved plans prepared by TEP, Drainage Statement prepared by EEC (Bruce Wilson P.E. sealed 12/31/2010), and Geotechnical Report prepared by Terracon (Oleg Lysyj sealed 12-10-10).
4) Install temporary construction fencing between proposed pole location and sub-embankment to southeast of the proposed pole at a distance as recommended by civil or geotechnical engineer.
5) Geotechnical Engineer and the Civil Engineer for the project shall be present during appropriate construction phases of the project to determine the proper construction steps are being followed. This shall include having a Geotechnical Engineer present for observations of soils encountered for the drilled shaft installation.
6) Free-fall concrete is not accepted for this project due to depth of pier. Bottom-dump hopper, or elephant trunk discharging concrete near hole bottom, shall be used.
7) Compaction testing is required before project begins and after pole installation is completed to show that the compaction surrounding pole is at, or exceeds, the existing compaction, and, is compacted to a density of not less than 95 percent of the maximum density and per PC/COT Standard Specifications (2003) section 203-9.03(B).
8) All unused materials, old lattice structure, and construction equipment must be removed from the parcel prior to final approval.
9) All disturbances due to the construction of this project within existing banks in the Santa Cruz River shall be mitigated to pre-construction condition to include: re-grading disturbed soils to pre-construction grades. Construction access or other activity shall not damage any existing bank protection.
10) PDSD Engineering Inspections are required prior to final floodplain inspection.
11) Inspection field reports are required and must be submitted to the City of Tucson Planning & Development Services Department (PDSD) Engineering Division. City Inspector may request the reports during inspections, however a copy must be provided with as-built submittal.
12) Submit final revised plan (as-built) to PDSD under the activity T10OT02668, prior to final inspection. Project closure documentation shall include as-built plans with elevations of top of concrete pad and adjacent finish elevations, testing reports from Geotechnical Engineer, and final completion statement from Civil Engineer.
13) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
14) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2011 CPIERCE1 OUT TO CUSTOMER Completed