Permit Number: T10OT00626
Parcel: 205640620

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T10OT00626
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/30/2010,

Mountain Vail Estates, Part G, Lots 339 thru 345 and 385 thru 501, C.A. "B" Grading Plan Comments:

1- It appears that the detention basin (between Lots 345 and 388) outlet elevation (i.e. bleed pipe) is lower than the Atterbury Wash 100-year water surface elevation, which might cause the basin not to operate properly. Show the erosion hazard setback line, on the Grading Plan, and revise the basin design to address the previously mentioned concern.
2- Show the Atterbury Wash cross section numbers on Sheet 5 of 8.
3- Revise the Wash cross section with overlapping information on Sheet 5 of 8.
4- Show the post development 100-year water surface elevations on Sheet 5 of 8.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/07/2010 SUE REEVES REJECT SHELF Completed