The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10EL00564
Parcel: 130070050

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00564
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/13/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
resubmittal for COT ID# 304 at 1310 South Alvernon Way (T10EL0564).

Sheet 1 of 8

No comments.

Sheet 2 of 8

1. Indicate how 1.66" dia. horizontal light arm support section is bent
from 13 to zero degrees off center where support arm connects to the
luminaire occurs.

Sheet 3 of 8

1. Notes (Bullet #5 & #6), Existing Electrical Riser Diagram & Elevation:
reduce the number of #12 replacement conductors between the panel and first
junction box and between the first junction box and second junction box from
six (6) to three (3) (consistent with original submittal).

2. Notes (Bullet #8) & Partial Plan View: reduce the number of #12
replacement conductors in the liquid tite cable between the second junction
box and the junction box on the opposite face from three (3) to two (2)
(consistent with original submittal).

3. Panel Schedule, Elevation, One-Line Diagram & Partial Plan View: reduce
number of lighting circuits from four (4) to (2) (consistent with original
submittal).

4. Notes (Left; #2): add clarifying phrase on exception for flexible cable
(e.g., " . except SOOW cable is to be used where conductors are enclosed in
the light arm supports between the connecting junction box and the
luminaire").

Sheet 4 of 8

No comments.

Sheet 5 of 8

1. Add notation that photometric data is continuation of that shown on
Sheet 6 of 8 for IES File 103328_L.

Sheet 6 of 8

No comments.

Sheet 7 of 8

1. Add notation that photometric data is continuation of that shown on
Sheet 6 of 8 for IES File 103328_R.

Sheet 8 of 8

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2010 SUE REEVES APPROVAL SHELF Completed
10/14/2010 CPIERCE1 OUT TO CUSTOMER Completed