Permit Number: T10EL00564
Parcel: 130070050

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00564
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. THIS PROJECT DOES NOT FOLLOW THAT OF PREVIOUS ELECTRICAL BILLBOARD PERMITS. CLARIFY.
03/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL00564, 1310 S Alvernon
Billboard Lighting Modification.

The electrical plans for this project have been denied for the following:

1. The lumen calculation has to be used against a stated size of property , per net acre. The calculation on sheet 3 of 4 on the electrical sheets, shows only lumen output of the fixtures to be installed.
2.Does the shield being installed on the fixture provide full cut off status.Provide documentation.
3. The existing panel is shown on the Partial Vicinity Map to be replaced, the Electrical Riser Diagram idicates use existing, will same one be used ?

Ray T Majuta, PDSD< City of Tucson,
Electrical Plan CK,
3/22/10
Ray.Majuta@tucsonaz.gov
04/06/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING MODIFICATION RESUBMITTAL FOR CLEAR CHANNEL BILLBOARD
COT ID #304 AT 1310 SOUTH ALVERNON WAY

Lighting Removal, Relocation and/or Replacement Site Plan

1. Billboard Notes: under Note #4, opening line should be amended to read
"Latitude and Longitude of billboard at approximate center of footprint:"
(also deleting line at bottom).
2. Billboard Notes: under Note #7, delete second bullet and associated
text ("Add new mounting C6x10.5 mounting rails (4 per face) attached with
bolts").
3. Billboard Notes: under Note #11, after "relocated", delete comma (as per
revised Site Plan Requirements).
4. Billboard Notes: delete Note #13 in its entirety.
5. Title Block: change title to "Lighting Modification Site Plan".
6. Add "COT Activity No. T10EL00564" near title block.

Light Mounting Detail (Sheet 2 of 4)

1. Sign Face Elevation: delete four pieces of new C6x10.5 rail shown.
2. Section A-A: delete two cross-section pieces of new C6x10.5 rail shown;
show light arm supports attached to existing stringers (or other existing
parts).
3. Rail Mounting Detail: delete this detail.
4. Plan View & Light Arm Mounting Detail: delete C6x10.5 rail and show
detail attaching light arm to existing stringer (or other existing part).
5. Scope of Work: delete second bullet on addition of new C6x10.5 rail.
6. Notes: under first bullet, delete reference to new members; change
compliance to International Existing Building Code as necessary.

Lighting Modification Plan (Sheet 3 of 4)

1. Billboard Notes: under Note #4, opening line should be amended to read
"Latitude and Longitude of billboard at approximate center of footprint:"
(also deleting line at bottom).
2. Billboard Notes: under Note #7, delete second bullet and associated
text ("Add new mounting C6x10.5 mounting rails (4 per face) attached with
bolts").
3. Billboard Notes: under Note #11, after "relocated", delete comma (as per
revised Site Plan Requirements)
4. Billboard Notes: delete Note #13 in its entirety.
5. Elevation & Electrical Riser Diagram: change dimension of EMT conduit
from ¾" to ½".
6. Partial Plan View: delete added GFCI and associated circuit.
7. Panel Block: delete reference to receptacle and associated entries.
8. Title Block: add title in title space ("Lighting Modification Plan").
9. Title Block: change "Drawing No. " to "Sheet".
10. Add "COT Activity No. T10EL00564" near title block.
11. Add flex cord detail (as previously provided on Pima County plans).

Photometric Data Sheet (Sheet 4 of 4)

1. Title Block: add title in title space ("Lighting Modification Plan
Photometric Data").
2. Title Block: change "Drawing No. " to "Sheet".

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/24/2010 SUE REEVES REJECT SHELF Completed