Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00204
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
06/23/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approv-Cond as noted on plans
07/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Comments below are for the lighting modification & electrical repair second
resubmittal for COT ID# 304 at 1310 South Alvernon Way (T10EL00204).

Sheet 2 of 2

1. Elevation & Electrical Riser Diagram: change gauge of conductors from
#10 to #12 to match the amperage of the circuits (20 amps). There is no
need for #10 conductors for any fixtures permitted by the settlement
agreement. [Note: as per the 6/23/10 email from LeeRay Hanly below, the EOR
has granted to permission to change the gauge of conductors from #10 to #12
on the plan. If that change is made (Elevation & Partial Riser Diagram) and
the unnecessary derating notations are struck as well, that would address
this comment]

2. PDSD staff notation or notice to be added to the plan or entered
administratively that installation of the number and gauge of conductors
shown on plan between panel box and first junction box to be confirmed by
field inspection prior to final inspection approval.

3. Comment for future reference: Panel Schedule: delete three spare
breakers and indicate three spaces instead.