| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 06/23/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | as noted on plans |
| 07/01/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Comments below are for the lighting modification & electrical repair second resubmittal for COT ID# 304 at 1310 South Alvernon Way (T10EL00204). Sheet 2 of 2 1. Elevation & Electrical Riser Diagram: change gauge of conductors from #10 to #12 to match the amperage of the circuits (20 amps). There is no need for #10 conductors for any fixtures permitted by the settlement agreement. [Note: as per the 6/23/10 email from LeeRay Hanly below, the EOR has granted to permission to change the gauge of conductors from #10 to #12 on the plan. If that change is made (Elevation & Partial Riser Diagram) and the unnecessary derating notations are struck as well, that would address this comment] 2. PDSD staff notation or notice to be added to the plan or entered administratively that installation of the number and gauge of conductors shown on plan between panel box and first junction box to be confirmed by field inspection prior to final inspection approval. 3. Comment for future reference: Panel Schedule: delete three spare breakers and indicate three spaces instead. |