Permit Number: T10EL00204
Parcel: 130070050

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00204
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON ELECTRICAL REPAIR RESUBMITTAL FOR CLEAR CHANNEL BILLBOARD COT ID
#304 AT 1310 SOUTH ALVERNON WAY

General comment

Billboard Modification Site Plan (Sheet 1 of 2)

1. Comment for future reference only: on Billboard Note #4, opening line
should be amended to read "Latitude and Longitude of billboard at
approximate center of footprint:" (also deleting line at bottom).
2. Comment for future reference only: change title to "Billboard
Electrical Repair Site Plan".
3. Comment for future reference only: add "COT Activity No. T10EL00204" at
the appropriate location (as per 3/30/10 meeting).

Electrical Plan Sheet (Sheet 2 of 2)

1. Elevation & Electrical Riser Diagram: change gauge of conductors from
#10 to #12 to match the amperage of the circuits (20 amps).
2. Elevation & Electrical Riser Diagram: delete two added wires for extra
circuit (one hot/one neutral).
3. Elevation & Electrical Riser Diagram: match replacement conduit to
existing (1/2" EMT).
4. Panel Block: correct stated amperes to match replacement panel box (60
amps).
5. Title Block: add appropriate title in title space ("Billboard Electrical
Repair Plan").
6. Title Block: change "Drawing No. 2 of 3" to "Sheet 2 of 3".
7. Add "COT Activity No. T10EL00204" in appropriate location.

AMENDED COMMENTS ON ELECTRICAL REPAIR RESUBMITTAL FOR CLEAR CHANNEL
BILLBOARD COT ID
#304 AT 1310 SOUTH ALVERNON WAY

Billboard Modification Site Plan (Sheet 1 of 2)

2. Comment for future reference only: change title to "Electrical Repair
Site Plan".

Electrical Plan Sheet (Sheet 2 of 2)

5. Title Block: add appropriate title in title space ("Electrical
Repair Plan").
04/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/12/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2010 DELMA ROBEY OUT TO CUSTOMER Completed
06/10/2010 SUE REEVES REJECT SHELF Completed