Permit Number: T10EL00204
Parcel: 130070050

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC

Permit Number - T10EL00204
Review Name: BILLBOARD-BLDG/ELEC
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/26/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Billboard Modification Site Plan

1. Indicate that Sheet 2 is not part of the submittal; alternatively, add
"Sheet 2 of 2" on the Authorized Repair plan sheet.

Sheet E1

1. Amend note on plan that reads "No parts or components are to be removed,
installed, replaced and/or reinstalled" to read "No parts or components are
to be removed, installed, replaced or reinstalled" (i.e., change the
"and/or" to
"or").
2. Electrical Riser Diagram: indicate the manufacturer and model number for
the replacement meter socket box.
3. Electrical Riser Diagram: indicate the number and gauge of existing and
replacement conductors.
4. Elevation: describe the point(s) and location(s) of connection between
the replacement EMT riser conduit and the existing conduit or junction boxes
to remain.
5. Panel Schedule: conform the height/width/depth dimensions to those of
the new 60A panel shown [Note: the dimensions shown are substantially
greater than manufacturer specs]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
03/12/2010 SUE REEVES REJECT SHELF Completed