Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC
Permit Number - T10EL00204
Review Name: BILLBOARD-BLDG/ELEC
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/26/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Billboard Modification Site Plan 1. Indicate that Sheet 2 is not part of the submittal; alternatively, add "Sheet 2 of 2" on the Authorized Repair plan sheet. Sheet E1 1. Amend note on plan that reads "No parts or components are to be removed, installed, replaced and/or reinstalled" to read "No parts or components are to be removed, installed, replaced or reinstalled" (i.e., change the "and/or" to "or"). 2. Electrical Riser Diagram: indicate the manufacturer and model number for the replacement meter socket box. 3. Electrical Riser Diagram: indicate the number and gauge of existing and replacement conductors. 4. Elevation: describe the point(s) and location(s) of connection between the replacement EMT riser conduit and the existing conduit or junction boxes to remain. 5. Panel Schedule: conform the height/width/depth dimensions to those of the new 60A panel shown [Note: the dimensions shown are substantially greater than manufacturer specs] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 03/12/2010 | SUE REEVES | REJECT SHELF | Completed |