Permit Number: T10CM03525
Parcel: 10709092A

Address:
515 W KELSO ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03525
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved see grading permit conditions.
01/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Detail 9/M2.0 is quite different from detail 1/1P2.0 even when only considering the referenced section of detail 9/M2.0 (e.g. meter, geometry of the bypass, pressure relief valve setting, etc.) Also, the plumbing plan (1P1.0) shows ½" piping in lieu the ¾" piping shown on the two details. Reference: Section 301.7, IPC 2006.[Clarify which make-up water detail is to be installed in the janitor's closet: 9/1M2.0 or 1/1P2.0. Reference: Section 106.3.1, IPC 2006.]
2. Comment not resolved. The listing information for the Clean Check assembly states: "Clean Check products are sold for the prevention of sewer backup and are not to be used for a cleanout." [Provide a cleanout at the junction of the building sewer and the building drain. Reference: Section 708.3.5, IPC 2006.]
3. Comment not resolved. The scuppers serving the 1800 square foot and the 2276 square foot roof areas appear to be too narrow to drain their respective roof areas. Provide the calculations used to determine the width of the weirs for these areas. [Provide calculations to support the primary scupper design with regard to the width of the scupper or provide structural calculations to show that the roof is capable of supporting the additional rain load caused by the increased ponding depth. (Note that a scupper acts as a weir, not a vertical or horizontal pipe.) Reference: Sections 1101.7, 1106.1, 1106.5, and 1107.3, IPC 2006, and Section 1611.1, IBC 2006.]
01/31/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/03/2011 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2011 CPIERCE1 OUT TO CUSTOMER Completed
02/11/2011 SUE REEVES REJECT SHELF Completed