Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM03257
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the new water pressure data supplied by Tucson Water indicates an available pressure range of either 41 - 48 PSI at the 1st Street meter or 40 - 47 PSI at the 4th Avenue meter. Neither pressure range is capable of supplying the required residual pressure for the specified water fountain. [Original comment: The specified drinking fountain, Haws 3500, requires a minimum flowing water pressure of 30 PSI for proper operation. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.] |
| 07/12/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/14/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/15/2011 | TERRY STEVENS | ZONING | REVIEW | Denied | Approval of the site plan is required prior to approval of the building plan. |
| 07/28/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/08/2011 | SUE REEVES | REJECT SHELF | Completed |