Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03257
Parcel: 117022420

Address:
941 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T10CM03257
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2010 DAVE MANN FIRE REVIEW Approved
11/19/2010 RONALD BROWN ZONING HC REVIEW Passed
11/22/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/22/2010 RONALD BROWN ADA REVIEW Approved
11/22/2010 JASON GREEN ENGINEERING REVIEW Approved
11/23/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. For additional fee assessment, please submit a letter summarizing all the deferred submittals to the Building Official: i.e. 1. Pre Engineered Steel Structure, 2. Shade Structure 3. Vortex Spray Pad Equipment and any other elements that are to be submitted at a later date.
a. Please insure that all structural foundation designs are included along with structural calculations.
END OF REVIEW
11/24/2010 GERRY KOZIOL WWM REVIEW Passed
12/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sheet 9 of 34 indicates the installation of a 1" potable water line running west from the new 2" potable water line, roughly 16 feet north of the branch serving the new drinking fountain. Clarify the termination point of this pipe and its proposed use. Reference: Section 103.2.3, UPC 2006.
2. The specified drinking fountain, Haws 3500, requires a minimum flowing water pressure of 30 PSI for proper operation. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.
3. Provide the model number of the proposed backflow preventer for the drinking fountain; detail 1, sheet 15 of 34, has an incomplete model number. Reference: Section 103.2.3, UPC 2006.
12/03/2010 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing potable water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
12/06/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE PROVIDE A SCHEMATIC FOR THE PUMP 1 AND PUMP 4 INTERLOCK (PP E6)
12/16/2010 TERRY STEVENS ZONING REVIEW Denied Approval of the site plan is required prior to approval of the building plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
01/05/2011 SUE REEVES REJECT SHELF Completed