Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM03018
Parcel: 11943001A

Address:
1655 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Need Special Inspection Certifications for review and approval
12/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project T10CM03018
1655 W AJO Wy
500KW Photovoltaic Systems

1. Need to provide information sheet on New Electrical Switching Cubicle,the information provided on electrical sheets is insufficient. If not available yet,plan review cannot be completed.
2. The conductors which will now feed the New Switching Cubicle then on to the existing Cubicle need to be identified.
Show type and size on plan.
3. The new Switching Cubicle is shown to be installed in a driveway, physical protection is required for the equipment.
4.Item #4 last review requested that the grounding electrode conductor to neutral tie be removed fron the exist Cubicle, because it was assumed that new Cubicle was now to be the main service now requiring it's own grouding system,is this the situation? Then a grounding detail needs to be drawn for new service equipment.
5. Voltage drop calculations ok.
6. Ok.
7. OK.
8. This item was not addressed sufficiently, a grounding note is shown on the DC side of the Inverter, however the new 1000 Amp Switch Gear (277/480v) should have it's own grounding system, and this grounding electrode conductor connected to the AC side of the Inverter.
9. OK.
10. Ok.
11. Item #11 last review not addressed,provide information sheet on new equipment.
12.Item #12 last review, KAIC ratings do not take the place of fusing or CB types.Indicate on plan these fuses or circuit breakers need to be equivalent for KAIC noted.
13. OK.
14. OK.
15. OK.
16. OK
17. 0K.
18. OK.
19. The 2005 NEC, Section 230.95, does not refer to fuse size, it refers to disconnect rating,thus the request for an information sheet on the 1000 amp SWgear.
20. OK.

Ray T Majuta,
City of Tucson,PDSD,
Elect Plan Ck,
12/13/10,
Ray.Majuta@tucsonaz.gov
12/17/2010 DROBEY1 ZONING REVIEW Needs Review
12/17/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2010 DELMA ROBEY OUT TO CUSTOMER Completed