Permit Number: T10CM02874
Parcel: 116193760

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02874
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2011 MARTIN BROWN FIRE REVIEW Approved
02/08/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Not so noticeable on the first submittal, but certainly prevalent with this submittal is the font size violation. As per our introductory Permit Preview Information of our web site and as per the City of Tucson Development Standards no. 2-01.2.3, the minimum font size allowed for all the drawing submittals is 3/32" for both upper and lower case. A majority of your drawings have fonts less than this requirement. Please revise all these drawings prior to the interior improvement submission. Please insure that all of your consultants do like wise.

END OF REVIEW
02/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
02/10/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed Shell only; no mechanical work
02/10/2011 ROBERT SHERRY WATER REVIEW Approved
02/10/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; provide the pipe sizing calculations. [Provide water pressure and water pipe sizing calculations. Include all fixtures and the estimated demand for HVAC equipment and process equipment when calculating the total demand and determining the pipe sizes. Reference: Section 610.1, UPC 2006.]
2. Comment not resolved. The natural gas piping appears to be based on a 2 PSI input with a 1.0 PSI pressure drop. If so, confirm that 2 PSI gas service is available from Southwest Gas and show the locations of the gas regulators and, if required, their vent pipes. [Provide a natural gas piping design, including a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference: Sections 103.2.3 and 1217.0, UPC 2006.]
3. Comment not resolved. The plumbing drawings for the roof of area B does not include the roof drainage information noted in your reply letter. [Provide roof drainage calculations and plans for areas B (primary and secondary) and C (primary) of the building. All roof areas shall be drained by roof drains, scuppers, or gutters. Reference: Section 1101.11.1, UPC 2006.]
4. Comment not resolved. Section 1101.11.2.1, UPC 2006 requires a minimum scupper width equal to the circumference of the roof drain required by Table 11-1, UPC 2006. [The architectural plans indicate that the overflow drainage for area C will be accommodated with overflow scuppers. Detail N7/A503 indicates a height of 4" for each scupper but does not show a width for each scupper. Provide the width for each scupper. Reference: Section 1101.11.2.1, UPC 2006.]
02/15/2011 GERRY KOZIOL WWM REVIEW Approved
02/25/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM02874
Building Plan (1st Review)

TRANSMITTAL DATE: February 25, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plan has been reviewed by Zoning Review Section and the plans appear to be approvable. Once Plumbing has reviewed and approved the building plan zoning will approve the plan.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm002874.doc
03/03/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied Prior to Engineering approval stamp, submit wall permit application.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2011 SUE REEVES OUT TO CUSTOMER Completed
03/10/2011 SUE REEVES REJECT SHELF Completed