Permit Number: T10CM02831
Parcel: 117070650

Address:
119 E 16TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T10CM02831
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-31-11
Activity: T10CM02831
Address: 119 E 16th St
Applicant: 3D Architecture

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Clarify the location of the posts and beams supporting the porch roof.

STRUCTURAL / FRAMING PLAN:
2. Specify roof slope for porch roof and provide roof covering material consistent with minimum slope criteria (Asphalt shingle require minimum 2:12), R905.2.7.
3. Show roof mounted equipment on the roof framing plan.

SECTIONS - DETAILS:
4. Provide uplift resistance for roof framing on garage trusses (hurricane clips), R802.11.1.
5. Specify all ledger connections to masonry walls (3x ledger material required), Figure R606.11(1).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review