Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02794
Parcel: 116193680

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02794
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/18/2010 RONALD BROWN HC REVIEW Approved RESUBMITTAL COMMENTS
SHEET C1
1. OK
2. OK
3. OK
4. Delete the flared wing on the side of the ramp.
NON COMPLIANT: AS PER ICC ( ANSI117.1) SECTION 406.6, FLARED SIDES MAY NOT PROJECT INTO ACCESS AISLES.

SHEET A1
5. Please provide large scale toilet plans showing all required dimensions and accessories for accessibility as required by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1).
THE MEN'S TOILET IS NOT ACCESSIBILE. OTHER FIXTURES (URNIAL) MAY NOT ENCROACH IN THE REQUIRED WATER CLOSET CLEARANCE AREA, ICC (ANSI 117.1), SECTION 604.3.2.

6. OK
7. OK
ADDITIONAL NOTE:
8. For the next submittal, please include all revised sheets in the full frawing set.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
11/22/2010 SUE REEVES REJECT SHELF Completed