| 11/18/2010 | RONALD BROWN | HC | REVIEW | Approved | RESUBMITTAL COMMENTS SHEET C1 1. OK 2. OK 3. OK 4. Delete the flared wing on the side of the ramp. NON COMPLIANT: AS PER ICC ( ANSI117.1) SECTION 406.6, FLARED SIDES MAY NOT PROJECT INTO ACCESS AISLES. SHEET A1 5. Please provide large scale toilet plans showing all required dimensions and accessories for accessibility as required by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1). THE MEN'S TOILET IS NOT ACCESSIBILE. OTHER FIXTURES (URNIAL) MAY NOT ENCROACH IN THE REQUIRED WATER CLOSET CLEARANCE AREA, ICC (ANSI 117.1), SECTION 604.3.2. 6. OK 7. OK ADDITIONAL NOTE: 8. For the next submittal, please include all revised sheets in the full frawing set. END OF REVIEW |