Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02794
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/18/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/18/2010 | RONALD BROWN | HC | REVIEW | Approved | RESUBMITTAL COMMENTS SHEET C1 1. OK 2. OK 3. OK 4. Delete the flared wing on the side of the ramp. NON COMPLIANT: AS PER ICC ( ANSI117.1) SECTION 406.6, FLARED SIDES MAY NOT PROJECT INTO ACCESS AISLES. SHEET A1 5. Please provide large scale toilet plans showing all required dimensions and accessories for accessibility as required by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1). THE MEN'S TOILET IS NOT ACCESSIBILE. OTHER FIXTURES (URNIAL) MAY NOT ENCROACH IN THE REQUIRED WATER CLOSET CLEARANCE AREA, ICC (ANSI 117.1), SECTION 604.3.2. 6. OK 7. OK ADDITIONAL NOTE: 8. For the next submittal, please include all revised sheets in the full frawing set. END OF REVIEW |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/22/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
11/22/2010 | SUE REEVES | REJECT SHELF | Completed |