Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02794
Parcel: 116193680

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02794
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned and/or operated project
10/07/2010 MARTIN BROWN FIRE REVIEW Approved
10/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/15/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
10/15/2010 RONALD BROWN ZONING HC REVIEW Denied SHEET C1
1. The ramp at 12' long and 1:12 slope has a rise of 12". As per 2006 IBC, ICC (ANSI 117.1), Section 405.8, it must have handrails on both side of the ramp and 3' clear between the handrails.
2. Extend the concrete curb across the North side of the bottom landing to stop a wheel chair stop from rolling into the PAAL.
3. The accessible parking sign is located in the wrong place. Please provide a large scale of the sign including "Van Accessible" signage.
4. Delete the flared wing on the side of the ramp.
SHEET A1
5. Please provide large scale toilet plans showing all required dimensions and accessories for accessibility as required by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1).

6. Provide a water dispenser as per 2006 IBC, Section 1109.5 and ICC (ANSI 117.1), Section 602.
7. The Break Room sink can be no higher than 2'-10" above the finished floor.
END OF REVIEW
10/15/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/15/2010 ROBERT SHERRY WATER REVIEW Approved
10/15/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations for the wall mounted condenser.
END OF REVIEW
11/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved