Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02794
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2010 | RONALD BROWN | ADA | REVIEW | Passed | Not a COT owned and/or operated project |
| 10/07/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/15/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 10/15/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | SHEET C1 1. The ramp at 12' long and 1:12 slope has a rise of 12". As per 2006 IBC, ICC (ANSI 117.1), Section 405.8, it must have handrails on both side of the ramp and 3' clear between the handrails. 2. Extend the concrete curb across the North side of the bottom landing to stop a wheel chair stop from rolling into the PAAL. 3. The accessible parking sign is located in the wrong place. Please provide a large scale of the sign including "Van Accessible" signage. 4. Delete the flared wing on the side of the ramp. SHEET A1 5. Please provide large scale toilet plans showing all required dimensions and accessories for accessibility as required by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1). 6. Provide a water dispenser as per 2006 IBC, Section 1109.5 and ICC (ANSI 117.1), Section 602. 7. The Break Room sink can be no higher than 2'-10" above the finished floor. END OF REVIEW |
| 10/15/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/15/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural calculations for the wall mounted condenser. END OF REVIEW |
| 11/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |