Permit Number: T10CM02692
Parcel: 138240790

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02692
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2010 DAVE MANN FIRE REVIEW Needs Review
11/24/2010 GERRY KOZIOL WWM REVIEW Approved
11/24/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied The appeal for the second level breakroom occupancy load change from 79 to 30 has been denied. Please redesign breakroom to be code compliant. Either add another exit stair or reduce the size of the room for a 1/15 = 30 occupant load.
11/29/2010 RONALD BROWN HC REVIEW Denied Reference Building Comments
11/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide documentation of the furring of the office exterior walls and provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope (e.g. call out the insulation for the furring and for the roof). Reference: Section 104.2, IECC 2006.
11/30/2010 ROBERT SHERRY WATER REVIEW Approved
11/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water pressure calculations to include the pressure drop due to the additional, 2" reduced pressure backflow preventer located at the building. Reference: Section 610.2, UPC 2006.
2. Fixtures located on floor levels above the first floor elevation of the building shall not drain through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.
3. Comment not resolved. The scupper width (6") appears to be too short to accommodate the design rainfall. Provide calculations to support the scupper design or provide structural calculations to show that the roof is capable of supporting the additional rain load. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006, and Section 1611.1, IBC 2006.
12/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02692
6601 S Renaissance Dr
Tucson Precision Products

The electrical plans have been denied for the following:

1. NEC 2005 230.2(c)(1) " Where capacity requirements are in excess of 2000 amperes at a supply voltage of 600 volts or less", then a second service can be permitted. Your plan indicates existing service at 909 amps, and new this permit at 965 amps totaling 1874 amps. Future Load inserted at 498 amps. Currently the total does not equal or surpass the 2000 amps required.
In this case you need to obtain "special permission" which requires an appeal to the Building Official.

Ray T Majuta,
PDSD, City of Tucson,
Elect Pln Ck,
12/05/10
Ray.Majuta@tucsonaz.gov
12/08/2010 GBONILL1 ZONING REVIEW Needs Review