Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL ADDITION
Address NEW:
6601 S RENAISSANCE DR
Apply Date:
09/27/2010
Applicant:
N/A
Description:
ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Architects:
  • WILSON, LAWRENCE R
Contractors:
  • WILSON AND ASSOCIATES DESIGN GRO

Permit Reviews

Permit Number - T10CM02692
Permit Status: Expired
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Start Date Submittal Complete Date Status  
01/10/2011 REVISION - - 1ST 01/25/2011 COMPLETED Review Details
04/19/2011 REVISION - - 2ND 04/19/2011 COMPLETED Review Details
04/19/2011 REVISION - - 2ND 05/10/2011 COMPLETED Review Details
04/27/2011 REVISION - - 3RD 04/27/2011 COMPLETED Review Details
05/10/2011 REVISION - - 2ND 05/10/2011 COMPLETED Review Details
09/27/2010 PLANS OK TO SUBMIT - COMM 09/27/2010 COMPLETED Review Details
09/28/2010 COMMERCIAL NEW 10/28/2010 COMPLETED Review Details
11/17/2010 RESUBMITTAL 12/08/2010 COMPLETED Review Details
12/08/2010 RESUBMITTAL 12/30/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM02692
Permit Status: Expired
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Outstanding Activity Conditions - 1
Date Name
09/27/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM02692
Permite Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
PLUMBING - GAS PRESS TEST FNL N/A Not Inspected
FIRE SPKLR - FINAL N/A Not Inspected
06/10/2011 ELECTRIC - PROGRESS N/A Partial Approval IVRS - Inspection :*
1) NO MORE THAN 300V TO GROUND BETWEEN DEVICES 404.8 (B)
2) TIGHTEN LOOSE FITTINGS
3) SECURE MC CABLE 6' INTERVALS
4) PROTECT END OF RACEWAY VDV CABLING FRO SHARP METAL EDGES
5) IDENTIFY FIRE ALARM BOXES
6) OK WALLS 105-111. BREAK ROOM UPSTAIRS AND AFTER CORRECTION
06/16/2011 ELECTRIC - CABLE DROP N/A Partial Approval IVRS - Inspection :*
1) RECEIVED GFI TEST
2) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT
3) NEED LETTER OR TORQUE
07/15/2011 FIRE - LANE SIGNS N/A Denied Fire apparatus access roads 20 to 28 feet shall have a Fire Access Road sign on both sides of road in the direction of travel. Roads greater then 28 up to 36 feet require a sign on one side in the direction of travel. The signs need to face both directions since the access road is not a one way street.

Completed Inspections

Permit Status: Expired
Permit Number: T10CM02692
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Completed Inspections - 43
Date Description Inspector Results Comments
01/03/2011 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
02/24/2011 PLUMBING - BACK WATER VALVE RRICH Approved IVRS - Inspection :*
1) 4" SEWER FROM BLDG TO TIE IN
02/24/2011 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
02/24/2011 PLUMBING - PRE SLAB RRICH Approved IVRS - Inspection :*
05/02/2011 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection :*
05/18/2011 EXCAVATION/LAYOUT REBAR & ZON MHENSON Approved IVRS - Inspection :*
05/25/2011 BUILDING PRE-SLAB MHENSON Approved IVRS - Inspection :*
06/03/2011 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
1) FROM METER THRU TO ALL UH UNIT SHUT OFF VALVES. 60 PSI TEST OK
2) RETEST TO 10 PSI FOR WATER HEATER VALVE INSTALL
06/20/2011 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED PER R. HOLLANDER
06/21/2011 SHEET ROCK NAILING MHENSON Approved IVRS - Inspection :*
06/23/2011 PLUMBING - ROOF DRAINS RRICH Approved IVRS - Inspection :* PROVIDE HANGERS AT NORTH WEST CORNER AS REQUIRED
06/24/2011 FIRE SPKLR - UG, PIPING, HYDRO DSIWARSKI Approved
06/24/2011 FIRE - HYDRANTS DSIWARSKI Approved
07/01/2011 RIGHT OF WAY - FINAL MCASTRO Approved
07/06/2011 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
07/06/2011 U VALUE FOR WINDOW MHENSON Approved IVRS - Inspection :*
07/06/2011 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
07/06/2011 NPPO - FINAL RDLD Approved
07/07/2011 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
07/08/2011 LANDSCAPE - FINAL RDLD Approved
07/15/2011 MECHANICAL - HOODS MRAMBER Approved IVRS - Inspection :*
07/15/2011 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
07/15/2011 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
07/15/2011 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
07/15/2011 ELECTRIC - OUTDOOR LIGHTING DSANTACR Approved IVRS - Inspection :*
07/15/2011 ELECTRIC - TEMPORARY SERVICE DSANTACR Approved IVRS - Inspection :*
07/15/2011 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
07/15/2011 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
07/18/2011 SIGN - FINAL RDLD Approved
07/19/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
07/19/2011 BUILDING ABOVE CEILING MHENSON Approved IVRS - Inspection :*
07/19/2011 FRAMING MHENSON Approved IVRS - Inspection :*
07/19/2011 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
07/19/2011 PLUMBING - PROGRESS RRICH Approved IVRS - Inspection :*
07/20/2011 CERTIFICATE OF OCCUPANCY MHENSON Approved IVRS - Inspection :*
1) WILL APPROVE WITH BLDG FINAL
07/20/2011 BUILDING - FINAL MHENSON Approved IVRS - Inspection :*
1) WILL APPROVE WITH CALLS FOR MECH, FIRE AND ENGINEERING
2) DABBS LIST DONE
07/20/2011 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
07/20/2011 STEM WALL/RETAINING WALL MHENSON Approved IVRS - Inspection :*
07/20/2011 BUILDING - PROGRESS MHENSON Approved IVRS - Inspection :*
07/20/2011 ROOF NAILING MHENSON Approved IVRS - Inspection :*
07/20/2011 EXT METAL CLIPS/EXT SHEATHING MHENSON Approved IVRS - Inspection :*
07/21/2011 ENGINEERING - FINAL RDLD Approved
07/21/2011 ENGINEERING - FINAL RDLD Approved