Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02502
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Condensate drains may not terminate over a roof drain unless the roof drain terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
| 09/27/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | With regard to detail 1/M-2, a vent pipe shall not be used as a waste pipe and an indirect connection of the waste from the hydrant is required. Reference: Sections 311.4 and 801, UPC 2006. |
| 09/28/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/29/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/29/2010 | ERIC NEWCOMB | HC | REVIEW | Approved | |
| 09/29/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/04/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |