Permit Number: T10CM02502
Parcel: 121060070

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02502
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02502
5609 E Speedway Bl
Auto Zone TI


The electrical plans have been denied for the following , please review address and comment on each:

1. Sheet E-1 indicates "add additional circuits if required,wire back to new Panel C if necessary for battery chargers".
If not sure provide new circuits on plan and indicate with circuit identification and provide load in panel schedule.
2. There are numeral referrals such as " add to existing circuit ". If it is unknown which circuit or if existing circuit can assume added load, then provide a new circuit and identify the panel and provide load.
3. The reference for the insta-hot water heater to be wired to existing circuit does not qualify as sufficient information. Provide circuit number, verify if sufficient and add load to schedule,
4. Sheet E-3 on lighting, appears that new lighting is being added to existing area as well as new, the IECC Lighting Budget Calculations indicate only 45 fixtures, however the lighting plan shows more than 132 according to lighting schedule showing new fixtures. Provide all fixtures in COM check calculation.
Presume only the new area fed by Panel C was being remodeled: please indicate what is new in the existing area.


Ray T Majuta
PDSD, City of Tucson,
Elect Plan Ck,
9/22/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/27/2010 SUE REEVES REJECT SHELF Completed