Permit Number: T10CM02502
Parcel: 121060070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02502
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2010 STEVE SHIELDS ZONING REVIEW Approved
09/08/2010 LOREN MAKUS ENGINEERING REVIEW Approved
09/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/09/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing, and termination of the condensate drains for the new roof top units.. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
09/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-1; KEY NOTES (17): NO STRUCTURAL DRAWINGS INCLUDED IN THIS SET. ARE CALCULATIONS REQUIRED? VERIFY.
2. SHEET A-1; FLOOR PLAN: PROVIDE CALCULATIONS FOR NEW MECHANICAL UNITS ADDED TO EXISTING STRUCTURE.
3. SHEET A-2; RESTROOM PLAN (6): THE ELEVATION REFERENCE 3/A-2 IS INCORRECT. REVISE.
4. GENERAL: A MINIMUM HEIGHT OF 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS PER CITY OF TUCSON STANDARDS (SEE SHEETS D-1/A-1/A-2/A-5/A-6).
09/09/2010 ROBERT SHERRY WATER REVIEW Approved
09/09/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Plumbing note F/P-1 specifies lavatory faucets with a flow rate of 1.0 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. In addition, accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2003, as amended by the State of Arizona.
09/09/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/09/2010 ERIC NEWCOMB ADA REVIEW Passed
09/09/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
09/10/2010 CPIERCE1 WWM REVIEW Needs Review
09/10/2010 DAVE MANN FIRE REVIEW Approved