Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02502
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/08/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/09/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, routing, and termination of the condensate drains for the new roof top units.. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
| 09/09/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-1; KEY NOTES (17): NO STRUCTURAL DRAWINGS INCLUDED IN THIS SET. ARE CALCULATIONS REQUIRED? VERIFY. 2. SHEET A-1; FLOOR PLAN: PROVIDE CALCULATIONS FOR NEW MECHANICAL UNITS ADDED TO EXISTING STRUCTURE. 3. SHEET A-2; RESTROOM PLAN (6): THE ELEVATION REFERENCE 3/A-2 IS INCORRECT. REVISE. 4. GENERAL: A MINIMUM HEIGHT OF 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS PER CITY OF TUCSON STANDARDS (SEE SHEETS D-1/A-1/A-2/A-5/A-6). |
| 09/09/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/09/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Plumbing note F/P-1 specifies lavatory faucets with a flow rate of 1.0 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. In addition, accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2003, as amended by the State of Arizona. |
| 09/09/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/09/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/09/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 09/10/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 09/10/2010 | DAVE MANN | FIRE | REVIEW | Approved |