Permit Number: T10CM02391
Parcel: 116193760

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02391
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The floor drains located in underground section of building C show traps without any venting. Neither traps nor vents are required if a sand separator is being installed. Reference: Section 1016.1.1, UPC 2006.
2. The under floor drawings show water distribution piping; if it is not to be installed under the slab, remove it from the drawing. Reference: section 103.2.3, UPC 2006.
3. Provide a vent for each fixture trap. Reference: Sections 901.0 and 910.1, UPC 2006.
4. Verify that there is sufficient depth available to combine the flammable vents and to combine the plumbing vents for the two flammable waste tanks. Reference: Sections 905.2 and 905.3, UPC 2006.