Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02391
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/16/2010 | CRAIG GROSS | ZONING | REVIEW | Approved | |
| 12/17/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the shell and core drawings are incomplete. The underground plumbing plans for areas A, B, and C do not have sufficient information to determine if the pipe sizes are correct or to determine how the future fixtures that are to be roughed-in at floor level (e.g. floor drains) are to be vented. Provide a list of the abbreviations used on the plumbing plans. Reference: Section 103.2.3, UPC 2006. 2. Comment not resolved. Detail 6/P801 calls for two flammable waste tanks to be placed in parallel but only one tank is shown on the plumbing plan. Show how the two units are to be installed on the drawing. Reference: Sections 103.2.3 and 1017.1, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/29/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/29/2010 | SUE REEVES | REJECT SHELF | Completed |