Permit Number: T10CM02391
Parcel: 116193760

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02391
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/16/2010 CRAIG GROSS ZONING REVIEW Approved
12/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; the shell and core drawings are incomplete. The underground plumbing plans for areas A, B, and C do not have sufficient information to determine if the pipe sizes are correct or to determine how the future fixtures that are to be roughed-in at floor level (e.g. floor drains) are to be vented. Provide a list of the abbreviations used on the plumbing plans. Reference: Section 103.2.3, UPC 2006.
2. Comment not resolved. Detail 6/P801 calls for two flammable waste tanks to be placed in parallel but only one tank is shown on the plumbing plan. Show how the two units are to be installed on the drawing. Reference: Sections 103.2.3 and 1017.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/29/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
12/29/2010 SUE REEVES REJECT SHELF Completed