Permit Number: T10CM02281
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02281
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2010 DAVE MANN FIRE REVIEW Approved
08/30/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET ASP1: ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON STANDARDS. REVISE.
2. SHEET A103; DETAIL 4: ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON STANDARDS. REVISE.
3. SHEET A200; PARTITION TYPES: FOR WALLS THAT STOP 6" ABOVE THE CEILING, PROVIDE DETAILS AT THE TOP OF THE WALL TO INDICATE DIAGONAL BRACING TO RESIST HORIZONTAL LOADS AS REQUIRED BY THE 2006 IBC, SECTION 1607.13. PROVIDE BRACE SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE.
4. SHEET A301; SECTIONS 1, 2, AND 3: PROVIDE CONNECTION INFORMATION FOR THE METAL STUD FRAMING/BRACING (KEYED NOTES 25, 26, AND 27).
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/31/2010 ROBERT SHERRY WATER REVIEW Approved
08/31/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006.
08/31/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
09/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
2. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
3. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the existing 4" waste pipe is now being served by a 3" cleanout).
4. The waste riser diagram shows three fixtures (8, 14, and 17) with indirect waste connections to the floor sink at the cashwrap; should fixture 17 be fixture 13?
09/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/20/2010 GERRY KOZIOL WWM REVIEW Denied needs waste water credit evaluation-5th floor 740-6602
needs IWC review/approval- Tom Tomchak, 443-6200- 5025 W Ina Rd
need to clarify if mop sink is direct- per plumbing fixture chart or indirect per isometric & plumbing plan?

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 SUE REEVES OUT TO CUSTOMER Completed
10/21/2010 SUE REEVES REJECT SHELF Completed