Permit Number: T10CM01987
Parcel: 12112060B

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T10CM01987
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2011 MARTIN BROWN FIRE REVIEW Approved
08/11/2011 RONALD BROWN H/C SITE REVIEW Denied 1. Not Used
2. Not Used
3. Detectable warning strips are not required to the entry of an accessible parking aisle.
4. As per table 1106.1 of the 2006 IBC, only 2 accessible parking spaces are required for a total of 44 parking spaces provided.
END OF REVIEW
08/11/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Window Depot
T10CM01987
Site Plan (Revision)

TRANSMITTAL DATE: August 11, 2011

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. D.S. 2-02.2.1.A.9 It appears that the Long-Term bicycle parking has be relocated and does not function as shown on the site plan. Relocate the Long-Term bicycle parking so that access to both doors is provided.

2. Once the above comments have been addressed Zoning is willing to provide an over-the-counter review. Please call or email to schedule and appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm01987

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan.
08/17/2011 LAITH ALSHAMI ENGINEERING REVIEW Approved
08/22/2011 ANDREW CONNOR NPPO REVIEW Approved
08/22/2011 ANDREW CONNOR LANDSCAPE REVIEW Approved
08/26/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2011 CPIERCE1 OUT TO CUSTOMER Completed
08/30/2011 SUE REEVES REJECT SHELF Completed