Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01750
Parcel: 117120470

Address:
54 W CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01750
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2010 DAVE MANN FIRE REVIEW Denied Two exits required. The 2 in front do not meet the 1/3 the diagonal distance apart required for sprinklered occupancies. Refer to 2006 IFC, section 1015.2.1, exception 2.
The rear exit does not meet the criteria because it is unacceptable to exit through a storage area. Additionally, panic hardware is mandatory except at the main entrance, and then it can be deleted if the requirements of 2006 IFC, section 1008.1.8.3, item 2 are met.
07/02/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Clarify the size of the drain piping at keynote 15, P-1; it is noted as an existing 2" waste pipe but it appears to have been serving the water closet that was removed as part of this activity and thus would have been either a 3" or 4" pipe. In addition, the specified grease interceptor has a 3" inlet which would constitute an obstruction of flow. Reference: Sections 103.2.3 and 311.5, UPC 2006.
3. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 3" grease waste entering the grease interceptor).
4. Clarify the design strategy for grease interception. The "Gravity Grease Interceptor Sizing" calls for a 690 gallon gravity grease interceptor but detail 203/P-3 shows a hydromechanical grease interceptor and a hydromechanical grease interceptor is specified on sheet P-5. Note that the sizing calculations for gravity grease interceptors are to be in accordance to the requirements of Section 1014.3.6, UPC 2006, using the drainage fixture units from Table 7-3, UPC 2006. Reference: Sections 103.2.3 and 1014.0, UPC 2006.
07/02/2010 ROBERT SHERRY WATER REVIEW Approved
07/02/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/13/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/14/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Commerical - Building comments
07/14/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per 2006 IBC, Section 1019 two exits are required.
a. As per section 1014.2.2, egress may not be through a kitchen or storage room.
b. As per section 1015.2.1, Exception 2, with a sprinkler system, the separation of the exit doors shall not be less than 1/3 the length of the maximum overall diagonal distance of the area served. The available distance between the frint doors is less than 1/3 of the diagonal.
c. Please provide panic hardware as per section 1008.1.9
d. Please rework your exits to meet all the requirements above.
2. Provide basement plan.
3. Provide and identify accessible seating throughout the dining area as per section 1108.2.8.
4. Provide dimensions for the accessibility clearances of new construction at the toilets.
a. The access to the men's toilet is not compliant. The distance between the lav and the new partition is less than the required 32" as per ICC (ANSI 117.1) Section 403.5.
b. The vestibule does not comply with Section 404.2.3.1.
5. Need Health Department review.
6. Provide structural details and calculations for :
a. All new roof top mounted HVAC equipment
b. All new interior hung fan coil units
c. Kitchen Exhaust Hood
7. Hot food service table to comply with ICC (ANSI 117.1, 2003 Edition), Section 904.5.
8. All new partitions must be braced to the structure above to comply with the 2006 IBC, Section 1607.13.
END OF REVIEW
07/16/2010 CPIERCE1 WWM REVIEW Needs Review