Permit Number: T10CM01441
Parcel: 11005021A

Address:
2959 N SWAN RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM01441
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2010 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
06/11/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
06/18/2010 STEVE SHIELDS ZONING REVIEW Approved
06/24/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied pp E-2 panel schedule for load center is calling for two different pieces of equipment with 2 different loads connected to same 220v disconnect.
If a/c unit is separate unit from equipment cabinet then please clarify on drawings how it is connected and provide load calculations including this equipment.
If hvac is part of the equipment cabinets listed assembly then please provide cut sheets for the cabinet and correct your panel schedule.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2010 CPIERCE1 OUT TO CUSTOMER Completed
07/16/2010 SUE REEVES REJECT SHELF Completed