Review Details: CELL TOWER/ANTENNAS
Permit Number - T10CM01441
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2010 | Michael Wyneken | PLANNING-CITY HALL | REVIEW | Approved | |
| 06/11/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Approved | |
| 06/18/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/24/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | pp E-2 panel schedule for load center is calling for two different pieces of equipment with 2 different loads connected to same 220v disconnect. If a/c unit is separate unit from equipment cabinet then please clarify on drawings how it is connected and provide load calculations including this equipment. If hvac is part of the equipment cabinets listed assembly then please provide cut sheets for the cabinet and correct your panel schedule. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/16/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 07/16/2010 | SUE REEVES | REJECT SHELF | Completed |