Permit Number: T10CM01146
Parcel: 133040030

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01146
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
05/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/04/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied THE PLANS FOR THE ADDITION OF THE SEWAGE LIFT STATION ARE OK ELECTRICALLY. UNFORTUNATELY YOU ARE SHOWING PANEL "LS" BEING CONNECTED TO AN EXISTING 1600 AMP SERVICE WHICH DOES NOT EXIST.

COMPLETE PLANS FOR THE SERVICE, THE UNDERGROUND TO THE FUTURE MODULARS, THE SITE LIGHTING & OUTDOOR LIGHTING CALCULATIONS MUST BE SUBMITTED FOR A COMPLETE REVIEW.