Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM01146
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/04/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/04/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | THE PLANS FOR THE ADDITION OF THE SEWAGE LIFT STATION ARE OK ELECTRICALLY. UNFORTUNATELY YOU ARE SHOWING PANEL "LS" BEING CONNECTED TO AN EXISTING 1600 AMP SERVICE WHICH DOES NOT EXIST. COMPLETE PLANS FOR THE SERVICE, THE UNDERGROUND TO THE FUTURE MODULARS, THE SITE LIGHTING & OUTDOOR LIGHTING CALCULATIONS MUST BE SUBMITTED FOR A COMPLETE REVIEW. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/07/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
05/07/2010 | SUE REEVES | REJECT SHELF | Completed |