Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM01120
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2010 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/03/2010 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 08/03/2010 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 08/03/2010 | GBONILL1 | ZONING HC | REVIEW | Approved | |
| 08/03/2010 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/17/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Several areas still provide exits for over 30, (124, 101). Per 2006 IBC, table 1017.1, corridors serving more than 30 occupants must be 1 hour rated. Plans do not indicate rated corridors. Reference previous comments 1 and 4. 2. The name of the selected inspector must be provided on the Special Inspection Certificate not the name of the company. Please correct the submitted certificate accordingly. 3. Special Inspector Certifications has been submitted for 4 items listed on sheet S1.2. There are a total of 6 special inspections listed. Please submit certifications for the remaining two. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/13/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |