Permit Number: T10CM01120
Parcel: 117062200

Address:
135 S 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM01120
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Several areas still provide exits for over 30, (124, 101). Per 2006 IBC, table 1017.1, corridors serving more than 30 occupants must be 1 hour rated. Plans do not indicate rated corridors.
07/14/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied A complete review of the resubmitted construction documents can not be completed until the following requirements have been meet:
1. Please provide two full sets of "bound" construction documents with revised sheets included.
2. Please provide 1 set of original submitted drawings for reference.
3. Please include all revised structural calculations in the calculation booklet.
4. Please provide two sets of complete structural calculations with all revisions included.
END OF REVIEW
07/14/2010 RONALD BROWN ZONING HC REVIEW Denied Please reference Commerical - Building comments
07/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Reducing the number of drain pipe size transitions does not eliminate the need for upper terminal cleanouts (e.g. P5 at the west end of room 124 and in room 104, P3 in rooms 121 and 122 (east side), the floor sinks in rooms 128 and 130, P6, and P4). Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
2. Comment not resolved. The submitted roof drainage calculations and plans do not meet the requirements of Sections 1101.11 and 1106.0, UPC 2006. Specifically, the gutters for roof sections 1 and 3 are too small (assuming a 1/16" slope per foot; at a slope of 1/8" per foot, the gutter for roof section 3 would be adequate but a slope of ½" per foot would be required for a 4"x 4" gutter to be adequate for roof section 1 - see Table 11-3, UPC 2006). Also, the scuppers for roof sections 2 and 5 need to have a minimum width of 9.4" (circumference of a 3" roof drain) - see Table 11-1, UPC 2006. All of the over flows must have the same capacity as the primary drain. Reference: Section 1101.11, UPC 2006.
07/15/2010 ROBERT SHERRY WATER REVIEW Approved
07/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The energy code compliance calculations (required only for the envelope of the building addition) are acceptable but there is insufficient information on the drawings to support the calculations. In addition, not all of the drawings are included in the submitted drawing set. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
07/28/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 135 S 4TH Av
CLS Plasma Tucson , 624
T10CM01120

The Electrical Plans have been denied for the following:

1. As per the previous request, compliance with The City of Tucson , Outdoor Lighting Ordinance # 10135 has not been provided . You have provided The 2006 IECC Exterior Lighting Budget Calculations. The City of Tucson Outdoor Lighting Ord #10135 is different and can be found on the City of Tucson Web Page, under Departments---- Planning and Development Services----Codes and Ordinances----- City of Tucson Outdoor Lighting Ordinance.
2. The resubmitted plan only has Electrical Sheets,E200,E300,E401,and E402, both sets are missing E001,E100,E101,E200,E300,E400,E500,E501and E502.

Ray T Majuta
PDSD, City of Tucson
Elect Plan Ck
7/28/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
08/02/2010 SUE REEVES REJECT SHELF Completed