Review Details: COMMERCIAL TI

Permit Number - T10CM01088
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER PER IBC TABLE 2902.1.
04/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide Type I hood for the range in the break room.
2. Show that the restroom exhaust fans are operating when the building is occupied.
3. Terminate the AC condensate drains in an approved location (i.e. not in a different suite).
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01088 5925 E Broadway

Denied for Electrical, following required.
1. 2006 IECC Lighting Budget Calculations needed.
2. Circuits OB 3 and 6 found in panel, not on power plan.
3. No maintenance receptacles for AC equipment on roof.
4. Homerun OB 7 should be #10.

Ray T Majuta,
PDSD, City of Tucson,
Elect Pln Review,
4/23/10,
520-837/4988
04/23/2010 ROBERT SHERRY WATER REVIEW Approved
04/23/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the waste and vent riser diagram.
2. Show how the water temperature for the lavatories is limited to 110 degrees Fahrenheit.
3. Provide a termination point for the water heater T&P relief located in the tenant space or the exterior of the building.
4. The first 8 feet of CW and HW for a water heater shall be insulated if the water heater does not have integral heat traps.
04/23/2010 ERIC NEWCOMB ADA REVIEW Passed
04/23/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENT.
04/27/2010 CAGUILA1 WWM REVIEW Needs Review
04/27/2010 CAGUILA1 ZONING REVIEW Needs Review
04/27/2010 CAGUILA1 ENGINEERING REVIEW Needs Review
04/27/2010 CAGUILA1 FIRE REVIEW Needs Review