Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00944
Parcel: 11706168A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00944
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The proposed gas-fired radiant heaters have a required clearance from combustibles of 17" on top, 46" in front, 8" in back, and 46" on the bottom. Considering the second floor has a ceiling height of only 96" and a width of 116", how will pedestrians be protected from the radiant heaters? Reference: Sections 106.3.1 and 912.2, IMC 2006.
06/09/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout at the base of each rainwater leader before it connects to a horizontal drain. Reference: Section 1101.12.2, UPC 2006.
2. Short radius quarter-bends are not allowed for use in rainwater drainage systems. Reference: Sections 706.4 and 1101.3, UPC 2006.
3. Coordinate the size of the sump pump discharge as shown in detail 3/P1.2 and pump specifications. Reference: Section 103.2.3, UPC 2006.
4. Revise the connection of the sump pump discharge to the horizontal drain line per Sections 710.4 and 1101.6, UPC 2006.
5. Provide calculations to show that the proposed sump pump system is capable of accommodating the drainage flow from a storm with a 60-minute duration and a 100-year return period (i.e. 3" per hour or 0.031 GPM/square foot). Reference: Sections 103.2.3 and 1101.11.0, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2010 DELMA ROBEY OUT TO CUSTOMER Completed
07/09/2010 SUE REEVES REJECT SHELF Completed