Permit Number: T10CM00944
Parcel: 11706168A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00944
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2010 GERRY KOZIOL WWM REVIEW Passed
04/09/2010 DAVE MANN FIRE REVIEW Approved
04/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Finish adding the sizes to the gas piping between GHU-09 and GHU-10.
04/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the evaporative cooling units. Reference: Section 302.1, IMC 2006.
2. Clarify the mounting method and the clearances (from combustibles and from the floor) for the gas-fired radiant heaters. Reference: Section 912.2, IMC 2006.
04/13/2010 ROBERT SHERRY WATER REVIEW Approved
04/19/2010 STEVE SHIELDS ZONING REVIEW Approved
04/22/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
04/26/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
04/28/2010 SUE REEVES REJECT SHELF Completed