Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00944
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2010 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 04/09/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/13/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Finish adding the sizes to the gas piping between GHU-09 and GHU-10. |
| 04/13/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the evaporative cooling units. Reference: Section 302.1, IMC 2006. 2. Clarify the mounting method and the clearances (from combustibles and from the floor) for the gas-fired radiant heaters. Reference: Section 912.2, IMC 2006. |
| 04/13/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/19/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/22/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/23/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 04/26/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 04/28/2010 | SUE REEVES | REJECT SHELF | Completed |